C7027A1049 Honeywell UV Flame Detector UPC Code: 085267038768.
Overview Compact flame detector for use with flame safeguard controls with ultraviolet amplifiers.
Features : ♦ Use with Honeywell Flame Safeguard primary safety controls and burners requiring ultraviolet flame detection. ♦ C7027 mounts on a 1/2 in. sighting pipe by using an integral collar. ♦ Detectors can be wired in parallel for difficult sighting applications. ♦ C7027 seals against pressures up to 5 psi (34.5kPa) when correctly installed. ♦ Allows for blast tube mounting due to compact size. ♦ C7044 mounts with a two screw bracket. ♦ The C7044 UV sensor tube is enclosed in a stainless steel housing. ♦ C7044 has the capability of side or end viewing in flame monitoring applications.
Specification : ♦ Type Ultraviolet, Minipeeper ♦ Application Coal fired burners ♦ Application Gas fired burners ♦ Application Oil fired burners ♦ Lead Length (in.) 96 in. ♦ Lead Length (mm) 2438 mm ♦ Electrical Connections 2 NEC Class 1 leadwires ♦ Ambient Temperature Range (F) 0 F to 215 F ♦ Ambient Temperature Range (C) -18 C to 102 C ♦ Vibration 0.5 G max ♦ Mounting Integral nut for 1/2 in. sighting pipe. ♦ Dimensions (in.) 1 1/16 in. diameter x 4 in. long ♦ Dimensions (mm) 27 mm diameter x 102 mm long.